AC Voltage including Sags and Surges: |
0 - 600V +/-(0.5% Rdg + 2 LSD) |
 |
AC Current: |
15 - 3000A (1000A standard CTs can be used as an option) +/-(0.5% Rdg + 2 LSD) |
 |
Power: |
Working (W), Reactive (VAR) and Apparent (VA) +/-(1.0% Rdg + 2 LSD) |
 |
Power Factor: |
0.00 - 1.00 |
 |
Energy: |
Working (kWh), Reactive (VARh) and Apparent (VAh) +/-(1.0% Rdg + 2 LSD) |
 |
Peak Demand: |
kW +/-(1.0% Rdg + 2 LSD) |
 |
Harmonics: |
THD, DC and individual up to 49th +/-(0.5% Rdg + 2 LSD) @ DC to 25 harmonics** |
 |
Frequency measurement: |
57 to 63.6Hz at 60Hz fundamental, 47 to 53Hz at 50Hz fundamental +/-(1.0% Rdg + 2 LSD) |
 |
Phase sequence: |
1-2-3 |
 |
Co-generation: |
Measures Absorbed and Generated Power and Energy |
 |
Selectable Fundamental Frequencies: |
50/60Hz |
 |
Available Recording Time: |
Several hours to several years depending on setup |